MITSUBISHI CONTROLLER SETUP

<< Click to Display Table of Contents >>

Navigation:  Multi-Protocol MasterOPC Server > MITSUBISHI SLMP PROTOCOL PLUGIN >

MITSUBISHI CONTROLLER SETUP

For correct operation of the OPC server, you must configure controller to work with the SLMP protocol. This can be done in GX Works.

Open GX Works, create a new project and specify type of controller used or open an existing project.

nastrojka_kontrollera_mitsubishi

In the project tree, open Parameter - Controller Name (e.g. FX5UCPU) - Module Parameter - Ethernet Port.

nastrojka_kontrollera_mitsubishi1

Select connection settings – Controller IP-address, mask and gateway, and protocol type - Binary.

nastrojka_kontrollera_mitsubishi2

Then click External Device Configuration.

nastrojka_kontrollera_mitsubishi3

Ethernet configuration page appears.

nastrojka_kontrollera_mitsubishi4

On this page, add an SLMP-connection. You can do this by dragging it to the table:

nastrojka_kontrollera_mitsubishi5

Then select TCP protocol and port - 5000 (port can be modified; this port must be specified in ОРС settings).

nastrojka_kontrollera_mitsubishi6

Now, configuration is finished. Click Close with Reflecting Settings.

Click Check on Module Parameter Ethernet Port to ensure that settings are correct and if all OK, click Apply.

nastrojka_kontrollera_mitsubishi7

Now, Mitsubishi controller setup is finished. You can upload application to the controller and check that variables can be polled correctly by OPC server.

Note. In order for the PLC to apply the settings, you must load settings into the controller, as well as reload the controller

Settings for UDP protocol

If you need to communicate with the controller via UDP, then you need to select this type of protocol, and you must also specify the IP address of the computer with the OPC server:

nastrojka_kontrollera_mitsubishi8

The rest of the settings are similar to the TCP mode settings.